Type R622 Pressure Reducing Regulator - First Stage Regulator
Type R622 direct-operated, spring-loaded regulators provide economical pressure reducing control in a variety of residential, commercial, and industrial applications. These regulators can be used with natural, manufactured, or liquefied petroleum gases and have the same inlet and outlet pressure capabilities.
Features
- Compact design
- High capacity
- Protective inlet screen
- Internal relief
- Light weight
- Inlet and out pressure gauge taps
Maximum Inlet Pressure
- Operating: 125 psig (8.62 bar)
- Emergency: 125 psig (8,62 bar)
- Except 1.8 to 2.2-inches w.c.(4 to 5 mbar) spring range which has operating and emergency pressures of 60 psig (4,14 bar)
Maximum Outlet (Casing) Pressure
- Operating to Avoid Internal Part Damage: 3 psid (0,21 bar d) above outlet pressure setting
- Emergency: 20 psi (1,38 bar
Time proven design constructed of corrosionresistant
and wear-resistant materials, the R622H is designed
to provide a Recommended Replacement Life of 20 years.
Built-in 1/8” FNPT gauge taps on both the inlet and outlet
pressure sides allow for easy system checks. A large 3/4”
FNPT drip-lip vent reduces the chance of blockage by freezing
rain or sleet when properly installed with the vent pointing
down. Each R622H is equipped for overpressure protection
with a corrosion-resistant internal relief valve that provides high
capacity relief and a travel stop on the closing cap. Its size and
con.guration make it ideal for under-the-dome installations.
First-Stage regulators reduce tank pressure to a lower pressure (usually 10 psig or 0,69 bar) for a Second-Stage regulator. Fisher First-Stage regulators are painted red for easy identi.cation. Vents are screened with standard orientation over the outlet. |